These excerpts taken from the C 10-K filed Feb 22, 2008. CHILLED WATER Landlord shall provide chilled water on a 24 x 7 365 days per year uninterruptible basis in accordance with the following specifications set forth as follows no higher than 42 degrees Fahrenheit in summer and no higher than 48 degrees Fahrenheit in winter. A maximum temperature delta of 12 degrees Fahrenheit and a minimum differential pressure of 20 psig will be maintained across the supply and return building risers valve outlets. 500 ton existing 24x7 connected load. CHILLED WATER Landlord shall provide chilled water on a 24 x 7 365 days per year uninterruptible basis in accordance with the following specifications set forth as follows no higher than 42 degrees Fahrenheit in summer and no higher than 48 degrees Fahrenheit in winter. A maximum temperature delta of 12 degrees Fahrenheit and a minimum differential pressure of 20 psig will be maintained across the supply and return building risers valve outlets. | EXCERPTS ON THIS PAGE: