This excerpt taken from the C 10-K filed Feb 22, 2008. EMERGENCY GENERATOR Specs: 1750 KW, 2188 KVA, 480Y/277 VOLTS Monthly 1. MAKE VISUAL INSP. OF GENSET & SURROUNDING AREA 2. OPEN DOORS & INSP. INTERIOR FOR LEAKS & LOOSE BELT 3. VISUALLY INSP. TRANSFER SWITCH & TIMERS 4. TURN SWITCH TO TEST POSITION & VERIFY GENSET START 5. PERFORM CALIBRATION & ADJUSTMENT ON GENSET 6. PERFORM MONTHLY COMPLIANCE RUN AND LOAD TEST 6. OBSERVE GENSET SUPPORTING LOAD 7. VERIFY GENSET GOES TO COOLDOWN TURNS OFF AFTER SET TIME 8. CLEAN AREA AROUND GENERATOR 9. MAKE FINAL INSP., CLOSE & LOCK ALL DOORS Quarterly 1. OBTAIN OIL AND FUEL SAMPLES FOR ANALYSIS 2. CALIBRATE ALL INSTRUMENTS 3. REPLACE OIL FILTERS 4. REPLACE AIR INTAKE FILTERS 5. TIGHTEN ALL CONNECTIONS IN CONTROL PANEL 6. PERFORM FUNCTIONAL TEST OF ALL SAFETIES Annual 1. PERFORM FULL FUNCTIONAL BLACKOUT TEST 2. PERFORM MAINTENANCE ON ATS SWITCHES 3. CONFIRM ELEVATOR OPERATION ON EMERGENCY POWER 4. PERFORM INSULATION RESISTANCE TESTING 5. PERFORM INFRARED SCAN OF EMERGENCY DIST GEAR UNDER LOAD. 6. PERFORM CHANGE OF LUBRICATION OIL
Sch-4-1
7. REMOVE COOLANT SAMPLE AND SEND FOR ANALYSIS |
| |||||||