C » Topics » Vertical Vibration: Not more than 15 milli(g) for gearless elevators and 20 milli(g) for geared elevators in the 1-10 Hz range measured in the vertical (Z) axis measured during full length of hoistway travel in either direction while elevator is in motion

These excerpts taken from the C 10-K filed Feb 22, 2008.

Vertical Vibration: Not more than 15 milli(g) for gearless elevators and 20 milli(g) for geared elevators in the 1-10 Hz range measured in the vertical (Z) axis measured during full length of hoistway travel in either direction while elevator is in motion.

Airborne Noise: Measured noise level of elevator equipment and its operation shall not exceed 50 dBA in elevator lobbies and 60 dBA inside car under any condition including door operation and car ventilation exhaust blower on its highest speed.

System Response Time (Elevator Nos. 1-20). Passenger waiting times in the passenger groups, as measured by registration of hall calls, shall meet the following criteria during all traffic conditions of the day other than “up peak”, after the equipment modernization and replacement is completed:

 

ELEVATOR GROUP

   REQUIRED
15-MINUTE
SYSTEM
RESPONSE
TIME
   REQUIRED PERCENTAGE OF REGISTERED
CORRIDOR CALLS ANSWERED IN ANY
15-MINUTE PERIOD
 
      £30
SECONDS
    £60
SECONDS
    £90
SECONDS
 

ELEVATORS 1-7

   £15    ³85 %   ³97 %   ³99.5 %

ELEVATORS 8-13

   £18    ³81 %   ³96 %   ³99 %

ELEVATORS 14-20

   £18    ³81 %   ³96 %   ³99 %

Vertical Vibration: Not more than 15 milli(g) for gearless elevators and 20 milli(g) for geared elevators in the 1-10 Hz range measured in the vertical (Z) axis measured during full length of hoistway travel in either direction while elevator is in motion.

Airborne Noise: Measured noise level of elevator equipment and its operation shall not exceed 50 dBA in elevator lobbies and 60 dBA inside car under any condition including door operation and car ventilation exhaust blower on its highest speed.

System Response Time (Elevator Nos. 1-24). Passenger waiting times in the passenger groups, as measured by registration of hall calls, shall meet the following criteria during all traffic conditions of the day other than “up peak”, after the equipment modernization and replacement is completed:

 

ELEVATOR GROUP

   REQUIRED
15-MINUTE
SYSTEM
RESPONSE
TIME
   REQUIRED PERCENTAGE OF
REGISTERED CORRIDOR CALLS
ANSWERED IN ANY 15-MINUTE
PERIOD
 
      £30
SECONDS
    £60
SECONDS
    £90
SECONDS
 

ELEVATORS 1-6

   £15    ³85 %   ³97 %   ³99.5 %

ELEVATORS 7-12

   £18    ³81 %   ³96 %   ³99 %

 

H-11


ELEVATORS 13-18

   £ 18    ³ 81 %   ³ 96 %   ³ 99 %

ELEVATORS 19-24

   £ 22    ³ 74 %   ³ 93 %   ³ 97 %

EXCERPTS ON THIS PAGE:

10-K (2 sections)
Feb 22, 2008
Wikinvest © 2006, 2007, 2008, 2009, 2010, 2011, 2012. Use of this site is subject to express Terms of Service, Privacy Policy, and Disclaimer. By continuing past this page, you agree to abide by these terms. Any information provided by Wikinvest, including but not limited to company data, competitors, business analysis, market share, sales revenues and other operating metrics, earnings call analysis, conference call transcripts, industry information, or price targets should not be construed as research, trading tips or recommendations, or investment advice and is provided with no warrants as to its accuracy. Stock market data, including US and International equity symbols, stock quotes, share prices, earnings ratios, and other fundamental data is provided by data partners. Stock market quotes delayed at least 15 minutes for NASDAQ, 20 mins for NYSE and AMEX. Market data by Xignite. See data providers for more details. Company names, products, services and branding cited herein may be trademarks or registered trademarks of their respective owners. The use of trademarks or service marks of another is not a representation that the other is affiliated with, sponsors, is sponsored by, endorses, or is endorsed by Wikinvest.