4.3.1.    Calculations of Annual Availability Performance Indices for Individual Voltage Classes

        Separate annual Availability performance indices shall be calculated for each Voltage Class and PTO as described below utilizing the Availability Measures discussed in Section 4.2.

57


Annual Average Forced Outage(IMS) Frequency for All Transmission Line Circuits (Index 1):

Fvc,k = 1
Nk
Nk
S    fik
i = 1
 

where

Fvc,k = frequency index for the Voltage Class, vc, (units = Forced Outages(IMS) /Transmission Line Circuit). The frequency index equals the average (mean) number of Forced Outages(IMS) for all Transmission Line Circuits within a Voltage Class for the calendar year k.

Nk =

number of Transmission Line Circuits in Voltage Class in calendar year k. See Note 2, Section 4.2.1.

fik =

frequency of Forced Outages(IMS) for the ith Transmission Line Circuit as calculated in accordance with Section 4.2.1 for calendar year k.

Annual Average Accumulated Forced Outage(IMS) Duration for those Transmission Line Circuits with Forced Outages(IMS) (Index 2):


Dvc,k

=

1

No,k

No,k
S    dik
i = 1

 

where

Dvc,k = duration index for the Voltage Class (units = minutes/Transmission Line Circuit). The duration index equals the average accumulated duration of Forced Outages(IMS) for all Transmission Line Circuits within a Voltage Class which experienced Forced Outages(IMS) during the calendar year k.

No,k =

number of Transmission Line Circuits in the Voltage Class for which the Forced Outage(IMS) frequency Availability Measure (fik) as calculated in accordance with Section 4.2.1 is greater than zero for the calendar year k. See Note 2, Section 4.2.1.

dik =

accumulated duration of Forced Outages(IMS) for the ith Transmission Line Circuit having a Forced Outage(IMS) frequency Availability Measure (fik) greater than zero for calendar year k as calculated in accordance with Section 4.2.1.

Annual Proportion of Transmission Line Circuits with No Forced Outages(IMS) (Index 3):

Pvc,k = Nk - No,k
Nk
   

where

Pvc,k = index for the proportion of Transmission Line Circuits for the Voltage Class with no Forced Outages(IMS) for the calendar year k.

Nk =

number of Transmission Line Circuits in Voltage Class for calendar year k. See Note 2, Section 4.2.1.

No,k =

number of Transmission Line Circuits in the Voltage Class for which the Forced Outage(IMS) frequency Availability Measure (fik) as calculated in accordance with Section 4.2.1 is greater than zero for the calendar year k. See Note 2, Section 4.2.1.

58


Wikinvest © 2006, 2007, 2008, 2009, 2010, 2011, 2012. Use of this site is subject to express Terms of Service, Privacy Policy, and Disclaimer. By continuing past this page, you agree to abide by these terms. Any information provided by Wikinvest, including but not limited to company data, competitors, business analysis, market share, sales revenues and other operating metrics, earnings call analysis, conference call transcripts, industry information, or price targets should not be construed as research, trading tips or recommendations, or investment advice and is provided with no warrants as to its accuracy. Stock market data, including US and International equity symbols, stock quotes, share prices, earnings ratios, and other fundamental data is provided by data partners. Stock market quotes delayed at least 15 minutes for NASDAQ, 20 mins for NYSE and AMEX. Market data by Xignite. See data providers for more details. Company names, products, services and branding cited herein may be trademarks or registered trademarks of their respective owners. The use of trademarks or service marks of another is not a representation that the other is affiliated with, sponsors, is sponsored by, endorses, or is endorsed by Wikinvest.