PCG » Topics » 4.3.2.1. CLs

This excerpt taken from the PCG 10-K filed Feb 18, 2005.

4.3.2.1.    CLs

        The calculation of the CLs for each of the three control charts is similar to the calculation of the annual Availability performance indices described in Section 4.3.1 except that the period for which data are to be included in the calculations is expanded from a single calendar year to the ten years, unless a shorter period is justified by the PTO, for the period immediately preceding the ISO Operations Date, or immediately preceding the date a TO becomes a PTO. To account for this change a count of Transmission Line Circuit years is included in the equations as shown below to enable derivation of CLs which represent average performance during a multi-year period.

CL for Annual Transmission Line Circuit Forced Outage(IMS) Frequency

    Y    Nk   Y    
CLfvc = S  S fik / ( S    Nk)    
    k-1 i-1   k=1    

where

CLfvc = center control line value for the Forced Outage(IMS) frequencies for each of the Transmission Line Circuits in the Voltage Class for Y years prior to the ISO Operations Date, or the date a TO becomes a PTO.

Y =

number of years prior to the ISO Operations Date (or the date a TO becomes a PTO) for which the PTO has reliable, continuously recorded Outage(IMS) data. Y=10 is preferred.

CL for Annual Accumulated Forced Outage(IMS) Duration for those Transmission Line Circuits with Forced Outages(IMS)

    Y    No,k   Y    
CLdvc = S  S dik / ( S    No,k)    
    k-1 i-1   k=1    

59


where

CLdvc = center control line value for accumulated Forced Outage(IMS) duration for each of the Transmission Line Circuits in the Voltage Class for Y years prior to the ISO Operations Date (or the date a TO becomes a PTO) in which the Forced Outage(IMS) frequency (fik) was greater than zero.

CL for Annual Proportion of Transmission Line Circuits with No Forced Outages(IMS)

    Y    
CLPvc = S    (Nk - No,k)
k=1
   
   
Y     
S  Nk
k=1    
   

where

CLPvc = center control line value for the proportion of Transmission Line Circuits in the Voltage Class with no Forced Outages(IMS) for Y years prior to the ISO Operations Date, or the date a TO becomes a PTO.
Wikinvest © 2006, 2007, 2008, 2009, 2010, 2011, 2012. Use of this site is subject to express Terms of Service, Privacy Policy, and Disclaimer. By continuing past this page, you agree to abide by these terms. Any information provided by Wikinvest, including but not limited to company data, competitors, business analysis, market share, sales revenues and other operating metrics, earnings call analysis, conference call transcripts, industry information, or price targets should not be construed as research, trading tips or recommendations, or investment advice and is provided with no warrants as to its accuracy. Stock market data, including US and International equity symbols, stock quotes, share prices, earnings ratios, and other fundamental data is provided by data partners. Stock market quotes delayed at least 15 minutes for NASDAQ, 20 mins for NYSE and AMEX. Market data by Xignite. See data providers for more details. Company names, products, services and branding cited herein may be trademarks or registered trademarks of their respective owners. The use of trademarks or service marks of another is not a representation that the other is affiliated with, sponsors, is sponsored by, endorses, or is endorsed by Wikinvest.