|
|
![]() | ![]() | ![]() | ![]() |
| |||||||||
This excerpt taken from the PCG 10-K filed Feb 18, 2005. SPECIFIC REQUIREMENTS
No line may be removed from service for greater than 30 days without prior notification to SCE. At least two independent transmission lines (one from SCE and one from SDG&E) between the transmission network (grid) and SONGS switchyard shall be in service at all times. (References 1, 2, 3, 4, 7, 8)
(References 2, 3, 4, 8)
79
Based on these nomograms and SONGS offline unit's status, if the Grid Control Center or ISO determines that the operating point is outside the applicable derated nomogram line, they shall notify SONGS immediately that a particular transmission line is out of service, and the critical system conditions are sufficient to cause SONGS off site power source to be considered INOPERABLE; i.e., unable to support SONGS voltage at 218 kV if the remaining unit trips. SONGS Control Room will declare the offsite source inoperable (in anticipation of losing the second SONGS unit) and will declare the time period within which the on-line unit will have to initiate shutdown if conditions are not corrected. The time period will be within 1 to 24 hours, based on the SONGS plant and equipment conditions. List of critical transmission lines/grid conditions: Critical Line(s) Out In SCE Territory Palo
Verde -Devers 500 kV Line Critical Line(s) Out in SDG&E Territory Hassayampa-N.
Gila 500 kV Line Critical
Grid Conditions: SCE/SDG&E
Tie Open, Unit 3 On-Line (Unit 2 Off-Line) Systems studies shall be performed and updated based on changing grid conditions (load growth, etc.) to identify critical conditions, such as the above cases, that could render the offsite power supply Inoperable. The offsite power system is considered Inoperable if it is degraded to the point that it does not have the capability to provide electrical support to safe shutdown loads and to mitigate the effects of an accident at SONGS. This level of degradation can be caused by an unstable offsite power system, or any condition which renders the offsite power supply unavailable for safe shutdown and emergency purposes. The following actions are required: 80 (References 1, 2, 19, 21) System studies shall consider the interconnections between SCE, SDG&E, and other utilities in the Western Electricity Coordinating Council (WECC). (Reference 7)
(References 14, 15, 16, 17, 26, 27)
(References 7, 20)
81
82 |
| |||||||